The Effect of Ambient Temperature on Components Performance of an In-service Gas Turbine Plant using Exergy Method

Singapore Journal of Scientific Research: Volume 1 (1): 23-37, 2011

F.I. Abam, D.C. Onyejekwe and G.O. Unachukwu

Abstract

Exergy analysis has been applied to 138 MW in-service gas turbine plant with data obtained from plant operation. The research investigated the effect of ambient temperature on the performance of the components system of the gas turbine plant using the exergy concept, to identify components that offer significant work potential saving opportunity. The fuel used is natural gas of low calorific value of 39.4 MJ m-3. The irreversibility rate of system components, exergy efficiency and the efficiency defects were determine for each component and for the entire plant at different temperatures. The results show a moderate increase of the total irreversibility rate of plant from approximately 415 to 421 KW while the rational efficiency decreased from 16.53 to 15.44% at same temperature range of 295 to 307 K. Furthermore, a 1°C increase in ambient temperature lead to 0.43 MW increase in the total irreversibility rate and 0.3% decrease in rational efficiency. The overall breakdown of plant, efficiency defect for ambient temperature range (295-307 K) stood at 83.475-84.56, 65.06-65.18, 3.23-3.33, 8.19-8.99 and 7.0-7.06% for combustion chamber, compressor, turbine and exhaust manifold, respectively. The exergy destruction rate in the combustion chamber and the turbine was about 36.4 and 5.4%, respectively. Our computation shows exergy efficiency value of 45.43 and 68.4% for both the combustion chamber and the turbine at 14°C increase in temperature. Overall suggestions for plant improvement are made as results show that the combustion chamber and turbine are the main sources of irreversibilities in the plant.

How to cite this article:

F.I. Abam, D.C. Onyejekwe and G.O. Unachukwu, 2011. The Effect of Ambient Temperature on Components Performance of an In-service Gas Turbine Plant using Exergy Method. Singapore Journal of Scientific Research, 1: 23-37.

DOI: 10.3923/sjsres.2011.23.37

URL: https://scialert.net/abstract/?doi=sjsres.2011.23.37

INTRODUCTION

The growing interests in energy efficiency and conservation have led to the development of advanced techniques for analysis of complex energy systems based on the second law of thermodynamics. One such performance analysis is based on the concept of exergy. An exergy-based system analysis is one that overcomes the limitations inherent in an energy-based analysis. Exergy is not conserved as energy but destroyed in the system, hence an exergy analysis assessing the degree of exergy destruction, identifies the location, magnitude and sources of system inefficiencies, (Flavio and Segioil, 2000; Zhang et al., 2000; Ebadi and Gorji-Bandpy, 2005; Rosen, 2001; Rosen and Dincer, 2004). Exergetic analysis allows thermodynamic evaluation of energy conservation, because it provides the tool for a clear distinction between energy losses to the environment and internal irreversibilities in the process (Mehmet and Ayhan, 2007; Prasada et al., 1995; Ahmet et al., 2006). This advantage gives information about the possibilities of improving thermal processes and quantifies irreversibilities in system components and their contribution towards the gross irreversibility of the entire plant. This gives opportunity for economic consideration and plant modernization for performance improvement.

The gas turbine plant used as a case study for this research is located in the city of Afam in Nigeria. The Afam thermal plant is the major thermal plant contributing substantially to the national grid-system and is regarded as the backbone in the National energy utility sector. A comprehensive exergy analysis to locate and identify components that offer significant work potential saving opportunity is important. This in-depth analysis was lacking in the work of Ofodu and Abam (2001) in which components efficiencies and the effect of intensive properties of the environment to irreversible losses were not properly identified, thus making it difficult to arrive at proper thermal suggestions for system improvement. In this study the effect of ambient temperature on irreversible losses in system components and the effect of turbine inlet temperature on exergy destruction rate on the entire plant are clearly identified. Mass and energy conservation laws were applied to system components and exergy balances for each component of the plant was presented.

BACKGROUND OF AFAM POWER STATION AND DATA COLLECTION

The Afam power station is located in Okoloma village in the oil rich Ndoki clan of Oyigbo in Rivers State of Nigeria. The Afam generating station is owned by the Power Holding Company of Nigeria Plc (PHCN). It has the biggest gas turbine plants in the country and is recently known as Afam Electric Power Business Unit (AEPBU). Afam power station consists of (20) gas turbines installed in five phases in sequence with the power demand increase. Afam II has 4 units BBC gas turbines, type 9C and total capacity of 95 MW. Afam III has 4 units BBC turbines, type 9C total capacity 109 MW. Afam IV has 6 units BBC turbine, type 13D and total capacity of 450 MW. Afam V has 2 units Siemens V94.2 and a total capacity of 276 MW. The turbine used for this research is GT 20 in Afam V with capacity of 138MW which was in-service at the time of this research from 2007 to 2009. During this period operational data were monitored and the daily monthly average data determined. Other data were obtained from operational log sheet in the previous year of 2006. The ISO or design data for Siemens V94.2 gas turbine plant used in this research are summarised in Table 1.

DESCRIPTION OF GAS TURBINE PLANT

The schematic of the 138 MW gas turbine system is shown in Fig. 1. The system consists of an Air-Compressor (AC), Combustion Chamber (CC) and the Turbine (GT). An exergy stream from the atmosphere in state 1 with ambient properties T0 and P0 enters the system through the axial flow compressor. Exergy in the form of mechanical work is supplied to the compressor through the turbine shaft. Due to irreversibilities, part of the exergy amount in the compressor is consumed in the process of work addition to the working fluid. The working fluid enters the combustion chamber at very high pressure delivery exergy. In the combustion chamber the fuel is another contributor of exergy.

The atomization of the fuel under high turbulence results into complex chemical process of the combustion chamber. The resultant effect of this is the flow of an exergy stream of hot gases under a very high pressure and temperature into the gas turbine.

Table 1: Gas turbine design parameters

Fig. 1: Work and exergy flow in gas turbine system

Again part of the exergy is destroyed in the turbine due to irreversibilities and finally the balance is partly utilized in driving the compressor, while the rest becomes available as the network produced by the turbine. The exhaust combustion gasses still contain a measure of exergy flow as they emerge from the turbine exhaust hoods. For Afam power plant the stream of exergy flow in the exhaust gases is wasted, since there is no heat recovery system.

EXERGY AND IRREVERSIBILITY ANALYSIS

The exergy balance equations and associated irreversibilities for various components system of the gas turbine plant are computed on the following assumptions of adiabatic conditions: (1) the combustion process is complete, (2) all components have adiabatic boundaries, (3) the mass flow of gas is constant throughout the cycle, (4) the exergy value of air entering the compressor is assumed zero since air is drawn from the atmosphere which is the reference state, (5) the reference state of air is at a temperature of 25°C and 1 atmosphere and (6) the air and the combustion products are assumed ideal characteristics.

The general exergy-balance equation applicable to any component of a thermal system from Kwon et al. (2001) is given by:

(1)

The term W and Q denote work and heat interactions in the system and Exloss is the lost work due to internal irreversibility which is give by:

(2)

Applying Eq. 1 to the components systems of the gas turbine and considering each of the components as a control volume the analysis is carried out as follows:

Compression process:

(3)

(4)

Exout, = exergy out flow from the air compressor Exc, for a mass flow rate to the combustion chamber:

(5)

(6)

(7)

The total irreversibility in the compressor is made up of two components mechanical irreversibility and process irreversibility (Kotas, 1995):

(8)

(9)

Where:

P2-1 = Internal power requirement of the compressor for a given mass flow rate
ηC = Isentropic efficiency of compressor
WC = Gross power input to the compressor

(10)

(11)

The total irreversibility in the compressor or exergy loss is given as follows:

(12)

(13)

Exergy efficiency of compressor is given as:

(14)

Combustion process: Applying the exergy balance equation in Eq. 1:

(15)

Es is shaft work and is exergy of fuel.

The exergy of fuel is a combination of physical (Exph) and chemical (Exch) exergy.

(16)

Where,

(17)

cp-h and cp-s are mean molar isobaric exergy capacity for evaluating enthalpy and entropy changes cp¯ in Eq. 17 is expressed or obtained in a polynomial form as:

(18)

The values of a, b, c and d are constant characteristics of the gas considered and obtained from standard tables.

(19)

where, xi = Mole fraction of constituent.

(20)

The exergy loss or irreversibility in the combustion chamber is obtained from (Nag, 2003):

(21)

(22)

The subscripts P, R, A and F represents, product, reactants, air and fuel and sP, sR, sA, sP are entropies respectively. Substituting Eq. 22 in Eq. 21 gives:

(23)

(24)

Substituting Eq. 24 in Eq. 23:

(25)

Applying ideal gas equation:

(26)

The rate of exergy loss is related with the Gibbs function and enthalpy of formation as:

(27)

and

(28)

(29)

where, β is the mass ratio of hydrogen to carbon in the fuel and mf and CV are mass flow rate of fuel and calorific value of natural gas. The exergy of combustion chamber which is the exergy out Excc can be evaluated by direct substitution in Eq. 15. Thus, combustion chamber exergy efficiency is evaluated as:

(30)

Expansion process: The exergy balance equation in the turbine is as follows:

(31)

The exergy inflow into the turbine is evaluated from Eq. 31. The internal power generated in the turbine is given by:

(32)

(33)

The mechanical irreversibility in the turbine is given by:

(34)

Thus, the effective power output from the turbine is:

(35)

Exergy output from the turbine is gotten as:

(36)

The rate of exergy dissipation or irreversibility in the turbine is given as:

(37)

The rate of exergy loss due to exhaust flue gases is given as:

(38)

(39)

The total exergy destruction or overall exergy loss in the plant is given as:

(40)

Efficiency defect of the plant is the summation of the efficiency defects of all the system components given as:

(41)

(42)

Where:

I = Irreversibility rate
Exfuel = Exergy of fuel

Fuel utilization efficiency: The fuel utilization efficiency is the ratio of all the useful energy extracted from the system to the energy of the fuel input.

(43)

The energy of the fuel input is given as:

(44)

Rational efficiency: The rational efficiency is also called second law efficiency. It is given as:

(45)

Exergy of fuel is obtained in Eq. 19.

RESULTS AND DISCUSSION

The design variables or ISO data for the 138 MW Siemens V94.2 gas turbine plant is summarised in Table 1. The composition of fuel (natural gas) used is also summarised in Table 2, with the approximate values of composition in mole percent and their standard exergy in KJ Kmol-1.

Figure 2 shows the irreversibility rates of the system components: compressor, turbine, exhaust manifold (diffuser) plotted against the ambient temperature. The irreversibility rate of compressor increases from 16090 to 1650 KW, combustion chamber from 324030 to 324620 KW, turbine from 40770 to 44 810 KW, diffuser from 34871 to 35182 KW and the total irreversibility rate of plant increases from 415766 to 42113 KW for 14°C increase in temperature. The result shows a high exergy destruction rate in the combustion chamber. However, a similar result is obtained in the work of Ahmet et al. (2006), which recorded large value of irreversibility in the combustion chamber for combine-cycle power plant.

Figure 3 depicts the percentage efficiency defect plotted against ambient temperature. The percentage defects for compressor, combustion chamber, turbine and diffuser ncreased from 3.23 to 3.33, 65.06 to 65.18, 8.19 to 8.99 and 7.00 to 7.06, respectively. While the overall rational efficiency decreased from 16.53 to 15.44 for 14°C increase in ambient temperature. The variation of exergy efficiencies of components system of gas turbine with ambient temperature is shown in Fig. 4. The exergy efficiency of compressor, combustion chamber and turbine decreased from 83.80 to 79.60, 48.60 to 45.43 and from 73.3 to 68.40, respectively.

Table 2: Composition of natural gas as it applies to Afam gas turbine plant
Ofodu and Abam (2001)

Fig. 2: Irreversibility rates of components versus ambient temperature

Fig. 3: Efficiency defects of components of power plant versus ambient temperature

Fig. 4: Exergy efficiencies of the components versus ambient temperature

While the total irreversibilty rate of the plant increased approximately from 415 to 421 MW and the rational efficiency decreased from 16.53 to 15.44%. It was observed that a 1°C increase in ambient temperature leads to a corresponding increase of 0.43 MW in the total irreversibility rate and 0.3% decrease in the rational efficiency of the plant.

Figure 5 shows the effect of 120 and 140% increase in turbine inlet temperature on plant rational efficiency and exergy destruction rate. An increase in the Turbine Inlet Temperature (TIT) caused a corresponding increase in the rational efficiency and decrease in exergy destruction rate. The change in exergy efficiency of system components of the plant for the same increase in TIT was also found to cause a slight increase in the exergy efficiency of turbine while the exergy efficiency of compressor remains constant, but a good increase in the exergy efficiency of combustion chamber was observed.

Fig. 5: The effect of change in turbine inlet temperature on the rational efficiency and exergy destruction in the plant

Fig. 6: Fuel utilization efficiency at full load against months of 2006

Also the amount of exergy destruction for 120 and 140% increase in TIT caused a decrease in the exergy destruction in the combustion chamber and the operation of the compressor was not affected. However, because of the large irreversibility in the combustion chamber, the overall exergy destruction in the plant decreases approximately of about 21.5%. It can be seen that the greatest exergy loss occur in the combustion chamber. The former findings are in concurrence with that obtained by Fiaschi and Manfrida (1998) and Habib et al. (1995).

Fig. 7: Fuel utilization efficiency at full load against months of 2007

The large exergy loss in the combustion chamber is associated with large temperature variation between the flame and the combustion fuel. A reduction in this temperature difference will cause a corresponding increase in turbine inlet temperature which will reduce exergy loss. The research shows that an increase in TIT above 100% will improve efficiency of the gas turbine plant between 2-6%. These conclusions aggress with the findings reported by Mahmoudi et al. (2009) and Ebadi and Gorji-Bandpy (2005). However, a higher value of TIT is required with technical considerations because of metallurgical limits of turbine blades material as presented by Kumar and Kale (2002).Figure 6 shows the variation of fuel utilization efficiency at full load for the year 2006 over the months of the respective year from January to December (1-12). The fuel utilization efficiency fluctuates over the months and the highest value is obtained at the month of June with 17.69%. Figure 7 shows for 2007 with highest value of about 17.51%. Figure 8 and 9 show the fuel utilization efficiency for 2008 and 2009 with maximum values of 17.7 and 17.59%, respectively. However, there is a fluctuation in the fuel utilization efficiency across the months which must have been influenced by the variation in intensive properties of the environment and large irreversibilities in the system components. However, calculations show that the fuel utilization efficiency and second law efficiencies are higher at full load condition as compared to part load.

The fuel utilization efficiency stood at about 18.6 and 14.4% at both full and part load respectively, while the second law efficiency was found to be about 16% and 11.5% at both full and part load conditions. In a similar work conducted by Prasada et al. (1995) in a cogeneration plant a higher value of fuel utilization efficiency of about 82 and 79.37% was obtained for both full and part load condition. And a second law efficiency of 33 and 16% was obtained for both full and part load conditions. This shows that the efficiency of a cogeneration plant is higher than a simple gas turbine plant that operates at the same capacity. This variation can be compensated for by modification of Afam power plant.

Between the periods 2006-2009 about 45% of the total generated power yearly is lost.

This poor performance of the system is attributed to poor maintenance procedures. Investigation has revealed that since the installation of the plant about 10 years ago, only the Combustion Inspection (CI) maintenance has been taking place and it is usually not regular.

Fig. 8: Fuel utilization efficiency at full load against months of 2008

Fig. 9: Fuel utilization efficiency at full load against months of 2009

Up till the time of carrying out this study, none of the turbines has undergone any HGPI (Hot gas path inspection) or MI (Main inspection). It is therefore this factor that must have been responsible for the gradual thermal deterioration of the plant losses that eventually led to poor performance and occasional break down.

CONCLUSIONS

A comprehensive study based on exergy analysis of Afam gas turbine plant and the effect of ambient temperature on performance parameters of the plant was presented. The overall exergy loss (efficiency defect) is evaluated to be 83.47 and 84.56% for ambient temperature values 295-307 K. The irreversibility rates of the combustion chamber is approximately 35% at ambient temperature of 295 K and 36.4% at 307 K ambient temperature while the irreversibility rate for turbine is approximately 4.5 and 5.4% at 295 and 307 K, respectively. In the plant the combustion chamber is the highest exergy consumer, thus it offers the largest improvement potential. The chemical reaction between air and fuel in the combustion process is responsible for such large exergy destruction in the combustion chamber. The second biggest consumer in exergy distribution (efficiency defect) is the turbine with 8.19-8.99%, for 295 to 307 K ambient temperature.

The research shows that exergy efficiency and exergy destruction rate are affected by the ambient temperature and the turbine inlet temperature. Based on this analysis the components that should be considered for improvement in the plant are the combustion chamber and turbine unit. An air intake cooling system (IAC) can be used in Afam gas turbine plant to improve the condition of air entering the compressor. Different techniques for power boosting through IAC includes: evaporative cooling, mechanical chiller, absorption chiller and thermal energy storage. Finally, for maximum efficiency of plant a system to increase the Turbine Inlet Temperature (TIT) is proposed using special super alloys in gas turbine hot parts. However, for this plant in question, the most attractive cooling technique would be air inlet chilling, since this can be achieved without changing the present plant configuration while all aspect of chilling may be externally applied.

NOMENCLATURE

Wc = Compressor Work (KW)
WT = Turbine Work (KW)
Wnet = Net power (KW)
cp = Specific heat capacity (KJ/KgK)
Qin = Input heat (KW)
ma = Mass flow rate of air (kg sec-1)
ΔG0 = Gibbs function
mf = Mass flow of fuel (kg sce-1)
cp-h = Mean isobaric enthalpy capacity (KJ/Kmol)
cp-h = Mean isobaric entropy capacity (KJ/Kmol.K)
h = Specific enthalpy (KJ kg-1)
P = Pressure (kpa)
R = Universal gas constant (KJ/KmolK)
T0 = Temperature, ambient (K)
ch = Chemical
I = Irreversibility (KW)
a = Air
δ = Efficiency defect

Subscripts:

f = Fuel
t = Turbine
g = Gas
ph = Physical
cc = Combustion chamber
c = Compressor

Greek symbols:

β = Mass ratio of hydrogen to carbon
ηc, ηT = Isentropic efficiency of compressor and turbin
n = Rational efficiency

References

Cihan, A., O. Hacihafizoglu and K. Kahveci, 2006. Energy-exergy analysis and modernization suggestions for a combined-cycle power plant. Int. J. Energy Res., 30: 115-126.
CrossRefDirect Link

Ebadi, M.J. and M. Gorji-Bandpy, 2005. Exergetic analysis of gas turbine plants. Int. J. Exergy, 2: 31-39.
CrossRefDirect Link

Fiaschi, D. and G. Manfrida, 1998. Exergy analysis of semi-closed gas turbine combined cycle. Energy conversion Manage., 39: 224-230.
CrossRef

Flavio, G. and A. Segioil, 2000. Thermodynamic evaluation of gas turbine cogeneration system. Energy conversion Manage., 41: 1191-1200.

Habib, M.A., S. Said and J.J. Al-Bagawi, 1995. Thermodynamic performance analysis of the Ghazlan power plant. Energy, 20: 1121-1130.

Kopac, M. and A. Hilalci, 2007. Effect of ambient temperature on the efficiency of regenerative and reheat Catalagzi power plant in Turkey. Applied Thermal Eng., 27: 1377-1385.
CrossRefDirect Link

Kotas, T.J., 1995. The Exergy Method of Thermal Plant Analysis. Krieger Publishing Co., Malabar, Florida, ISBN: 0-89464-941-8.

Kumar, N.A. and S.R. Kale, 2002. Numerical simulation of steady state heat transfer in a ceramic-coated gas turbine blade. Int. J. Heat Mass Transfer, 45: 4831-4845.
CrossRef

Kwon, Y., H. Kwak and S. Oh, 2001. Exergeoeconomic analysis of gas turbine cogeneration system. Int. J. Exergy, 1: 31-40.
CrossRef

Mahmoudi, S.M.S., V. Zare, F. Ranjiban and L. Garooci-Farshi, 2009. Energy and exergy analysis of simple and regenerative gas turbines inlet air cooling using absorption refrigeration. J. Applied Sci., 9: 2399-2407.
CrossRefDirect Link

Nag, P.K., 2003. Power Plant Engineering. Tata McGraw-Hill, New Delhi.

Ofodu, J.C. and D.P.S. Abam, 2001. Exergy analysis of Afam thermal power plant. Nig. Soc. Eng. Technol. Trans., 37: 14-28.

Prasada, R., P.J. Utgikar and S.P. Dubey, 1995. Thermo-economic analysis of gas turbine co-generation plant. J. Power Energy Proc. Inst. Mech. Eng., 209: 45-53.

Rosen, M.A., 2001. Energy and exergy based comparison of coal fired and nuclear steam power plants. Exergy Int. J., 3: 180-192.
CrossRef

Rosen, M.A., and I. Dincer, 2004. Effect of varying dead-state properties on energy and exergy analysis of thermal systems. Int. J. Thermal Sci., 43: 121-133.
CrossRef

Zhang, G., B. Hua and Q. Chen, 2000. Exergeoecomic methodology for analyzing of process system. Comput. Chem. Eng., 24: 163-618.
CrossRef