Asian Science Citation Index is committed to provide an authoritative, trusted and significant information by the coverage of the most important and influential journals to meet the needs of the global scientific community.  
ASCI Database
308-Lasani Town,
Sargodha Road,
Faisalabad, Pakistan
Fax: +92-41-8815544
Contact Via Web
Suggest a Journal
Applied Energy
Year: 2010  |  Volume: 87  |  Issue: 10  |  Page No.: 2994 - 3004

Energy conservation measures in an institutional building in sub-tropical climate in Australia

M.M. Rahman, M.G. Rasul and M.M.K. Khan    

Abstract: In this study, various energy conservation measures (ECMs) on heating, ventilating and air conditioning (HVAC) and lighting systems for a four-storied institutional building in sub-tropical (hot and humid climate) Queensland, Australia are evaluated using the simulation software called DesignBuilder (DB). Base case scenario of energy consumption profiles of existing systems are analysed and simulated first then, the simulated results are verified by on-site measured data. Three categories of ECMs, namely major investment ECMs (variable air volume (VAV) systems against constant air volume (CAV); and low coefficient of performance (COP) chillers against high COP chillers); minor investment ECMs (photo electric dimming control system against general lighting, and double glazed low emittance windows against single-glazed windows) and zero investment ECMs (reset heating and cooling set point temperatures) are evaluated. It is found that the building considered in this study can save up to 41.87% energy without compromising occupancies thermal comfort by implementing the above mentioned ECMs into the existing system.

View Fulltext    |   Related Articles   |   Back
 
 
   
 
 
 
  Related Articles

No Article Found
 
 
 