HOME JOURNALS CONTACT

Journal of Applied Sciences

Year: 2005 | Volume: 5 | Issue: 9 | Page No.: 1582-1588
DOI: 10.3923/jas.2005.1582.1588
Diagnosis of Shunt Faults in Power Distribution Feeders and Laterals
Y lmaz Aslan

Abstract: In this study, a digital fault location and monitoring technique using fibre-optics and current sensors for overhead power distribution systems is presented. By using lateral current data transferred through fibre-optic communication lines to the substation, the possibility of multiple fault point locations are eliminated. The technique, based on an interactive approach whereby an assumed fault point is varied systematically until the actual fault point is found, has culminated in a fault locator design that gives a high accuracy for the vast majority of practically encountered system and fault conditions. The effectiveness of this method is verified through Electromagnetic Transients Program (EMTP) simulations.

Fulltext PDF Fulltext HTML

How to cite this article
Y lmaz Aslan , 2005. Diagnosis of Shunt Faults in Power Distribution Feeders and Laterals. Journal of Applied Sciences, 5: 1582-1588.

Related Articles: